Rotary Field Indicator 8120
|
| |
Characteristics:
|
- Extended Rotary Indicator Device
- Rotary Field Indicator with Phase Indication
- Highest Safety CAT IV / 1000 V
- Voltage Range 100…1700 V Phase to Phase
- Indication of Phase Under Voltage Failure
- or Connection of Neutral
- Developed for Utility Companies, Electric Power
- Substation, Generators, Wind Power Stations,
- Solar Power Converter
- Incl. CAT IV – Test Leads and Probes
- Incl. rubber holster for rough environments
- Safety acc. IEC/EN 61010-1, IEC/EN 61557-1, IEC/EN 61557-7
|
|
Technical data:
|
- Voltage Range
- Frequency Range
- Display
- Test Current
- Duration Time (DT)
- Pollution Degree
- Measurement Cat.
- Safety
- Power Supply
- Dimension
- Weight
|
- 100…1700 V AC (Phase/Phase)
- 40…450 Hz
- 6 LED
- < 3.5 mA
- Continuous Operation
- 2
- CAT IV / 1000 V against Earth
- IEC/EN 61010-1,
- IEC/EN 61557-1
IEC/EN 61557-7
- no batteries required
- approx. 220 x 110 x 45mm
- approx. 480 g
|
| |
|
|
| |
Function Examples:
|
|
| |
Connection L1, L2, L3 -
|
Indicates Phases and Right Rotary Field R |
| |
Connection L1, L1, L3 -
|
Phase Indication is blinking and Triangle appears |
| |
Connection L1, L2, N -
|
Phase Indication L3 is blinking and Triangle appears |
| |
|
|
|
Scope of Supply:
|
|
| |
1 pc HDT Xtroid 8120 3 pcs Test Leads 3 pcs Test Probes 1 pc Instruction Manual
|
| |
|
|
|
Order information:
|
|
| |
Description: HDT Xtroid 8120 Order No.: 8120
|
| |
|
|
| |
Pictures:
|
|
| |
|
|
Download:
|
|
| |
Data Sheet Instruction Manual |
|