Professional Voltage Testers from HDT

The voltage tester is the most important tool for the electrician; he uses it to determine the absence of voltage on operationally live parts and trusts its safe function for the rest of his life. Voltage testers are divided into single-pole (also called phase testers) and double-pole voltage testers, which provide a safe test result.

The highest safety requirements are shown in a special standard for two-pole voltage testers, the EN 61243-3 in its current version 2014.

Furthermore, there are non-contact voltage testers, which are mainly used in the American market and to search for cable breaks. They are not suitable for reliably detecting the absence of voltage.

The product range of simple voltage testers consists of low-priced models that have basic functions and comply with current safety standards.

HDT is the world's leading OEM/ODM manufacturer of voltage testers and offers suitable products for every application, which are described below.

As the market leader in 2-pole voltage testers, we cover the requirements for highest safety and most comprehensive functions - from the beginner to the professional. Also available with your housing!

Basic 2-pole Voltage Testers

The range of basic Voltage Testers consists of low-cost models that have standard functions and comply with the latest safety standards.

Model 3002 3003 3009 3011 3020 3025 3303
Display 11 LEDs (+12, -12, 24, 50, 120, 400, 690V 8 LEDs (+12, -12, 24, 50, 120, 230, 400, 690V) 4 Neon light bulbs 4 LED 5 LEDs (-5, +5, +12, +24, +48V)
Voltage Range 12…690V AC/DC 120, 240, 277, 480V AC
160, 330, 380, 600V DC
50, 120, 230, 400V AC/DC  5…48V AC/DC
Polarity Indication automatic ̶ automatic
Frequency Range 0...65 Hz
Input Current < 3,5 mA < 3,5 mA (690 V AC); < 6 mA (1500 V DC) < 3,5 mA < 10 mA
Single Pole Voltage 100...690 V AC ̶
Rotary Field Test 120…690 V 120…1000 V      
Continuity/Diode Test optical and acoustical ̶
Measurement Category CAT III / 600V, CAT IV / 300V CAT III / 600V CAT II / 600V ̶
Protection Degree IP 54 IP 40 ̶
In Compliance with EN 61010, EN 61243-3:2014 EN 61243-3:2014, IEC 61010-1 EN 61010-1 EN 61010-1, EN 61326
Certification CE CSA ̶ CE
Battery Test Connect both tips ̶
Battery 2 x 1,5V AAA, LR03 ̶
Length of Cable approx. 1,2 m ca. 1 m approx. 1 m approx. 1,2 m ̶ approx. 1 m
Dimension approx. 205 x 67 x 27 mm approx. 205 x 55 x 21 mm approx. 150 x 32 x 26 mm approx. 122 x 22 x 17 mm
Weight approx. 130 g approx. 115 g approx. 50 g

2-pole "ProCompact" voltage testers

2-pole voltage testers are the most important tool for every electrician. The model without load buttons is very compact but still has all important functions and is certified for highest safety according to EN61243-3.

Model 3030 3031 30315 3034
Display 12 LEDs 12 LEDs, 3 Digit LCD 13 LEDs, 3 Digit LCD 12 LEDs, 4 Digit LCD
Voltage range ±12, 24, 50, 120, 230, 400, 690 V LED: ±12, 24, 50, 120, 230, 400, 690, 1000 V
LCD: 1000 V AC, 1500 V DC
LED: ±12, 24, 50, 120, 230, 400, 690 V
LCD: 1000 V AC, 1500 V DC
Backlight n/a line
Polarity indication automatic
Frequency range 16…400 Hz
Input current < 3,5 mA < 3,5 mA (690 V AC); < 6 mA (1500 V DC)
Single pole test 90...690V AC 90...1000 V AC
Rotary field indication 120…690 V 120…1000 V
Continuity/Diode test optical and acoustic
Resistance line 0...1999 Ω
Overvoltage category CAT IV / 600V, CAT III / 1000V
Protection degree IP 64
In compliance with EN 61010, EN 61243-3:2014
Certification CE
Battery test Connect both tips LowBat in LCD Display
Battery 2 x 1,5V AAA
Length of cable approx. 1,2 m
Dimension approx. 240 x 65 x 19 mm
Weight approx. 170 g approx. 180 g

Professional 2-pole "ProRCD" voltage testers

The models with load switch (load buttons) are the top products in the HDT portfolio of 2-pole voltage testers and, in addition to a wide range of functions such as frequency measurement or resistance measurement, offer the possibility of connecting a load for tripping a residual current circuit breaker or resolving ghost voltages. This is done according to the standard via the two-hand operation of the load buttons in the main body and test probe of the voltage tester.

Model 3037 30375 30376 30377 30379 30378
Display 12 LEDs, 3 Digit LCD 13 LEDs, 3 Digit LCD   13LEDs
Voltage Range LED: ±12, 24, 50, 120, 230, 400, 690 V
LCD: 6-690 V AC/DC
LED: ±12, 24, 50, 120, 230, 400, 690, 1000 V
LCD: 6-1000 V AC, 1500 V DC
LED: ±12, 24, 50, 120, 230, 400, 690, 1000 V
LCD: 0,5-1000 V AC, 1500 V DC
LED: ±12, 24, 50, 120, 230, 400, 690, 1000 V
Backlight ̶ ̶
Polarity Indication
Low Voltage Mode ̶ ̶
TRMS Voltage measurement ̶ ̶
Crest Faktor ̶ 1...10V: CF>2.5
>10...300V: CF=5
>300...500V: CF=3
>500...750V: CF=2
>750: CF=1.5
̶
Frequency Range 16…400 Hz 16…950 Hz
Input Current < 3,5 mA < 3,5 mA (690 V AC); < 6 mA (1500 V DC)
Single Pole Test 90...690V AC 90...1000 V AC
Rotary Field Indication 120…690 V 120…1000 V
Continuity/Diode Test
Forward voltage display for diode test ̶ ̶
Resistance measurement ̶ 0...1999 Ω ̶
HOLD Function ̶ ̶
Frequency range ̶ 1…950 Hz ̶
NCV ̶ ̶
RCD trip test
Overvoltage Category CAT IV / 600V, CAT III / 1000V
Protection Degree IP 64
In Compliance with EN 61010, EN 61243-3:2014
Certification CE, optional TÜV GS
Battery Test Indication in LCD display ̶
Battery 2 x 1,5V AAA
Length of cable approx. 1,2 m
Dimension approx. 240 x 75 x 30 mm
Weight approx. 270 g

Professional 2-pole voltage testers "ProCleanTec

The new fields of application, solar or e-car, have extended the requirements for the safety of voltage testers. This is reflected in the highest protection class in the low-voltage range, CAT IV 1000V (see also FAQ CAT IV 1000V). HDT offers models in the classic compact design of the 2-pole voltage tester with main body and long test probe as well as models that combine 2 slim test probes with a compact main body.

Model 3038 3039
Display 13 LEDs 13 LEDs, 4 Digit LCD
Voltage Range LED: ±12, 24, 50, 120, 230, 400, 690, >1000 V LED: ±12, 24, 50, 120, 230, 400, 690, 1000 V
LCD: 1000 V AC, 1500 V DC
Backlight n/a
Polarity Indication automatic
Frequency Range 16…400 Hz
Input current < 3,5 mA (690 V AC); < 6 mA (1500 V DC)
Single pole test 90...1000 V AC
Rotary field indication 120…1000 V
Continuity / Diode test optical and acoustical
Overvoltage category CAT IV / 1000 V
Protection degree IP 64
In compliance with EN 61010, EN 61243-3:2014
Certification CE
Battery Test Connect both tips LowBat in LCD Display
Battery 2 x 1,5V AAA
Length of cable approx. 1,2 m
Dimension approx. 240 x 75 x 30 mm
Weight approx. 270 g

Current-voltage tester

The current-voltage tester cannot be described in any other way than as the Swiss army knife for the electrician. In a slim design, the function of current testing is added to the classic functions of a 2-pole voltage tester. Certified according to EN61243-3!

Model 3610 3611
LCD with back light 7-Segment 4 digit Display
LEDs +120V, -120V, 230V, 400V, 690V, 1000V
Voltage Measurement 1.....1000V AC TRMS, 1.....1500V DC
Vibration motor Yes
Auto Start Options Voltage, Continuity
Current Measurement 0,1....200 A AC, 40...65 Hz; Resolution 0,1 A 0,1....200 A AC/DC, 45...65 Hz; Resolution 0,1 A
Single Pole Phase Test >90V....1000 V +/-10%, 50/60 Hz
Phase Rotation Test  100....1000 V +/-10% (L-L), 50/60 Hz
Resistance measurement 0....100 kΩ; Resolution1Ω < 2 kΩ; 1 kΩ > 2 kΩ
Continuity Test <500 kΩ, Continuity buzzer in resistance mode: <20 Ω
Diode test Continuity test
Cable break detector by NCV Yes, with sensitivity bargraph and different sound patterns
Frequency Measurement Yes, 0 - 800 Hz
Torch light Yes
Self test Yes
Duty Cycle 10 sec. on / 240 sec. off
Current Consumption  <3.5 mA @ 1000 V AC
Low bat indication Yes
Auto Power Off Yes
Test leads 19 mm distance; Storage on back side
Fork opening 14 mm
In compliance with IEC 61243-3:2014, IEC 61010-1:2010
Certificate CE
IP protection IP 64
Overvoltage Category CAT IV / 600 V, CAT III / 1000 V
Battery 2 x 1,5V AAA

Voltage testers with IP2X tip protection

A further feature of 2-pole voltage testers are models with protected test probes. Originally required by the EDF in France, the metal tips have an insulating protective sheath which must first be removed for measurement by spring force or 2-hand release. This is to prevent possible short circuits. And according to the latest standard EN 61243-3, higher loads than the 3.5 mA at 230 V are also permissible, for example to trigger a residual current circuit breaker.

Model 3612 3613
LCD with back light 7-Segment 4 digit Display
LEDs Continuity, ELV/ Single Pole, Rotary Field; +120 V, -120 V, 230 V, 400 V, 690 V, 1000 V
Voltage Measurement 1.....1000V AC TRMS, 1.....1500V DC
Vibration motor Yes
Auto Start Options Voltage, Continuity
Current Measurement 0,1....200 A AC, 40...65 Hz 0,1....200 A AC/DC, 45...65 Hz
Single Pole Phase Test >90V....1000 V +/-10%, 50/60 Hz
Phase Rotation Test  100....1000 V +/-10% (L-L), 50/60 Hz
Resistance measurement 0....100 kΩ; Resolution 1Ω < 2 kΩ; 1 kΩ > 2 kΩ
Continuity Test <500 kΩ, Continuity buzzer in resistance mode: <20 Ω
Diode test Continuity test
Cable break detector by NCV Yes, with sensitivity bargraph and different sound patterns
Frequency Measurement Yes, 0 - 800 Hz
Torch light Yes
Self test Yes
Duty Cycle 10 Sek. on / 240 Sek. off
Current Consumption  <3.5 mA @ 1000 V AC
Low bat indication Yes
Auto Power Off Yes
Test leads IP2X test tips with 19mm distance; Storage on back side
Fork opening 14 mm
In compliance with IEC 61243-3:2014, IEC 61010-1:2010
Certificate CE
IP protection IP 64
Overvoltage Category CAT IV / 600 V, CAT III / 1000 V
Power supply 2 x 1,5V AAA

Non-contact voltage testers

Non-contact voltage testers detect the electric field strength emitted by a conductor or other live parts such as sockets. This is then indicated to the user by means of an LED, a sound generator and/or a vibration motor. However, this only works with AC voltage and not with DC voltage.

HDT offers a wide range of products here, from simple analogue voltage detection to rotary field detection in the 3-phase network and digital interference filter.

See all non-contact voltage testers

Accessories for voltage testers

An essential accessory for the voltage tester is, for example, the "Proving Unit" required in the UK, which generates a test voltage with which the function of the voltage tester can be verified before use.

How and where can I order these voltage testers?

HDT works exclusively as an OEM/ODM manufacturer and is constantly developing the portfolio further - for innovative and competitive products for your brand.
From an order quantity of 100 units, the voltage testers can be customised to your requirements, for example by changing the housing colours and the device printing.

The packaging can be designed according to your wishes. You determine the languages of the operating instructions as well as the address of the contact person.
Typical delivery times are 4-8 weeks from Hong Kong or Serbia.

The products are developed in Europe and tested in Germany by our quality assurance department. TÜV-GS marks are available for some products.
As a specialist in electrical test and measurement equipment, we place a high value on safety and ease of use. Our products are exclusively available under customer brand.

CONTACT

 

Technical knowledge area

You will find many questions and topics on the subject of "Measuring and Testing" on the FAQ pages.